Pump off: When the pump is off the Auxiliary 3-way Valve keeps the valve in a closed position.

Starting sequence: The pump starts against a closed valve. When the working pump rate is reached the Solenoid Control gradually opens the valve to prevent pump surge.

Stopping sequence: The pump stops when the valve is totally closed. The shut-off signal de-energizes the Solenoid Control to let the valve close gradually. Meanwhile the pump is still working. When the valve is fully closed the Switch Assembly shuts the pump off.

Emergency sequence: In case of a power failure (P2 > P1), the valve closes fast to protect the pump. The Pressure Relief Valve or Surge Anticipator Valve is usually combined with the pump control valve in order to dissipate surge pressures.

Included accessories:
  • Valve position indicator X101
  • Gauge cock CSA-12, Rp 1/2" (upstream)
  • Pressure gauge [0-16 bar]
  • CLA-VAL 60-31 Technical Specifications

    Flanged(mm) DN50 DN65 DN80 DN100 DN125 DN150 DN200 DN250 DN300 DN350 DN400 DN450 DN500 DN600
    L 230 290 310 350 400 480 600 730 850 980 1100 1200 1250 1450
    F 145 170 170 235 295 295 400 510 600 712 712 712 900 900
    H 195 225 230 305 365 375 460 547 695 821 821 900 1035 1035
    H1(PN10) 82.5 93 100 110 125 142.5 170 200 227.5 252.5 282.5 325 370 430
    H1 (PN16) 82.5 93 100 110 125 142.5 170 200 227.5 260 290 325 370 430
    H1 (PN25) 82.5 93 100 117.5 135 150 180 212.5 242.5 277.5 310 335 370 430
    Hm 255 295 300 390 470 480 585 700 875 1030 1030 1200 1310 1310
    A 190 200 200 200 235 250 270 290 365 400 425 450 520 520
    B 145 150 150 160 160 165 200 200 345 385 380 420 460 460
    øC 45 60 60 60 60 80 80 80 80 80 80 80 - 120
    Weight(Kg) 15 20 25 40 60 70 120 190 330 540 640 700 980 1080
    